History

Originally founded as the Leicester School of Art in 1870, the university has evolved through many incarnations including the Leicester Colleges of Art and Technology and Leicester Polytechnic. Leicester Polytechnic officially became De Montfort University on 26 June 1992.

The building is over 120 years old and has seen many changes in its time. It was formally occupied by banking group Alliance & Leicester PLC as their main headquarters. It now forms part of the vast De Montfort University campus.

Works

The UPS upgrade works at Heritage house consisted of installing an 400a bypass switch panel. Supplied from existing UPS Panel in 4core 35mm XLPE/SWA/PVC cable. The panel has 2no 400a three phase and neutral 60947-3 isolator switches, one being an input isolator and one an output isolator with a bypass switch that allows the UPS unit to be isolated for maintenance purposes without interruption to the site load. An outgoing 4core 35mm XLPE/SWA/PVC cable supplies an 160a WIB panel with 4no 160a three pole and Neutral 60947-2 MCCB isolator switches. 2no outgoing BS EN 50525-2-11 SY cable suppling CSS C1T 60 P UPS 1 and 2no outgoing BS EN 50525-2-11 SY cable suppling CSS C1T 60 P UPS 2. All the supplies are installed on a 300mm heavy duty galvanised tray, mounted using 41mm x 41mm Unistrut with 6mm roofing bolts, washers, and channel nuts.

1no Distribution board upgrade fitted with Schneider Acti9 Isobar P 18way 125a three phase and neutral distribution board supplied by a 4core 35mm XLPE/SWA/PVC cable from existing Essentials Busbar 125a tap off. New supplementary bonding has been installed to all new tray work and panels.

The De Montfort University UPS system comprises of 2 x Riello Central Supply System 60kVA.

UPS units (Part No: CSS C1T 60 P), that are working as a parallel UPS system. The UPS system has been installed complete with 1 x separate floor mounted battery cabinet (Part No: BB 1900 480V V9), which contains 40 x SWL3300FR Yuasa lead acid batteries. The battery runtime has been specified for 11 minutes at a rated load of 108kW for the UPS system. The battery system has been installed with a separate wall mounted DC isolation WIB panel, that allows the DC supply to be independently isolated. The UPS system has also been installed with a separate wall mounted bypass panel (rated at 400A), that allows the UPS unit to be isolated for maintenance purposes without interruption to the site load.

The UPS unit has been fitted with a network adapter communication card that provides Modbus network signals from the UPS unit.

See below photos of the work.